What size wire for 20 amps at 100 feet?

10 AWG copper · 8 AWG aluminum240 V single-phase, 3% max drop, non-continuous load

V
A
ft
%
Auto uses 60 °C for 100 A and below, 75 °C above.

ResultsWire Size

The short answer

For a 20 amp load 100 feet from the panel on a 240 V single-phase circuit, use 10 AWG copper or 8 AWG aluminum. That keeps voltage drop at or under 3% and meets NEC Table 310.16 ampacity at the 60 °C terminal rating.

Voltage drop decides the size here. The smallest copper wire rated for 20 A is 12 AWG, which would drop 3.29% over 100 ft. That's over the 3% guideline, so the next size up is needed.

If the load is continuous (on for three hours or more, like heaters, EV chargers and lighting), the conductor must be rated for 125% of the load, or 25 A. That calls for 10 AWG copper.

20 amps at 100 feet on other systems

SystemCopperAluminumDrop (copper)
120 V single-phase8 AWG6 AWG2.6%
240 V single-phase10 AWG8 AWG2.07%
208 V three-phase10 AWG8 AWG2.07%
480 V three-phase12 AWG10 AWG1.43%

Three-phase systems carry the same current with less voltage drop, so they often allow a smaller conductor over the same distance.

20 amps at other distances (240 V copper)

DistanceCopper sizeGoverned by
25 ft12 AWGampacity
50 ft12 AWGampacity
75 ft12 AWGampacity
100 ft10 AWGvoltage drop
150 ft8 AWGvoltage drop
200 ft8 AWGvoltage drop
250 ft6 AWGvoltage drop
300 ft6 AWGvoltage drop

How this was calculated

Voltage drop = 2 × K × I × L ÷ CM = 2 × 12.9 × 20 × 100 ÷ 10,380 = 4.97 V (2.07% of 240 V)

K is 12.9 for copper and 21.2 for aluminum. CM is the conductor's area in circular mils. Distance is one-way. Change any input in the calculator above to check your own circuit.

These sizes assume no more than three current-carrying conductors in the raceway and 30 °C ambient. Derate under NEC 310.15 for more conductors or hotter locations, and size motor circuits under Article 430.

Open the full wire size calculator with these numbers

Results are estimates for planning and education. Verify against the current code edition your jurisdiction has adopted, manufacturer data and a licensed professional before you build or install.